This is an interlock plate rather than a switch: a machined aluminum piece that slides behind the panel cover so the main breaker and a dedicated generator breaker cannot both be on. The listing says it suits Square D vertical 150 or 200 amp panels where the gap between the main and the generator breaker is 3-1/4 to 4 inches.
That fitment line is the whole story. Check your panel's make, orientation and the exact spacing before ordering, because a plate that does not match will not lock out correctly. Compared with the Tzechkii disconnect box, the plate costs little and adds no new enclosure, but it needs a spare breaker slot, a dedicated generator breaker and a proper inlet wired by an electrician.
The listing describes corrosion resistance and anodizing. Over years of ownership, the main thing to watch is a loose mounting screw. Verify the interlock is accepted by your inspector, as some jurisdictions want a listed kit for the panel. The plate also asks something of the household: the generator breaker has to be switched on only after the main is off, in that order, every time. A laminated card taped inside the panel door, written in plain steps, turns that rule into a habit for anyone who might use the generator in an emergency.
What works
- Physically stops both breakers being on
- Anodized aluminum construction
- No separate enclosure to mount
- Targets Square D vertical 150/200A panels
Watch out for
- Fits only a specific panel and spacing
- Needs a dedicated breaker and inlet
- Inspector may want a listed kit
Spec sheet
- Fits
- Square D vertical 150 or 200 amp panels
- Spacing
- 3-1/4 to 4 inches between main and generator breaker
- Material
- Aluminum alloy, anodized
- Function
- Interlock between main and generator breaker
- Finish
- Blue




